We
have developed special activated carbons to remove volatile organic
compounds (VOC), formaldehyde and other chemical substances (patent
no. 3050139).
Compared with regular activated carbons, special activated carbons
have a greater ability to adsorb chemical substances and generate
less than 1/5th the amount of dust.
Space velocity
6100h-1
18400h-1
Name of substance
Regular
activated carbons
Special
activated carbons
Regular
activated carbons
Special
activated carbons
inlet
outlet
inlet
outlet
inlet
outlet
inlet
outlet
n-Octane
277.6
14.6
174.8
<0.2
184.3
15.0
188.1
<0.2
n-Nonane
87.8
<0.2
31.9
<0.2
50.6
5.8
51.3
<0.2
a-Pinene
121.6
4.1
22.5
<0.2
40.5
3.6
33.0
<0.2
3-Carene
30.7
<0.2
12.2
<0.2
32.7
<0.2
23.1
<0.2
1,2,3-Trimethylbenzene
35.8
<0.2
18.0
<0.2
35.7
<0.2
30.2
<0.2
2-Ethyltoluene
19.8
<0.2
12.7
<0.2
18.4
<0.2
21.2
<0.2
Fenchone
13.5
<0.2
6.8
<0.2
12.3
<0.2
11.3
<0.2
*Special activated carbons
A water-glass (sodium silicate) coating affords this type of activated
carbons superior
removal ability, while restraining the amount of dust generated.
Restraining the outgassing from the components used in the Environmental Medical Center is one crucial factor in reducing the concentration of chemical substances.
(1) :
Exclusive Air Handling Unit (AHU) for the Environmental Medical Center
A double outer plate has been adopted for Environmental Medical Center AHU.
Stainless steel (SUS) 304 that has been subjected to degreasing is used for coils, fins, and inner plates.
The bearings of the AHU and fans are equipped with a sealing mechanism to prevent the inflow of air from the outside(patent no.3025965).
(2) :
Metal parts
Phosphoric acid and alkaline are used for degreasing.
(3) :
Filters
No-binder filters are used
(4) :
Inorganic joint exclusively for the Environmental Medical
Center (patent no.3045093)
Parts
Surface Finish Material
Floors
Granite & Special inorganic joint
Walls
Enameled steel panel
Ceiling
Air Ducts, Air Distribution
Equipment, Air Volume amper
Degressed SUS304
Duck Packing
Teflon packing
Sound Attenuafor
Degressed SUS wool sound attenualor
Windows
Electromagnetic-wave-shielding glass
HEPA & Medium Effcienty Filter
No-binder filters
Air Handing Unit
Degressed SUS304
Fans
Degressed SUS304
We developed a system to monitor the concentration of chemical substances indoors. Measurements are taken with a hydrocarbon analyzer that was improved points by setting measurement points accordingly; a personal computer stores the measured data.
Data Display
Monitoring System
*Challenge tests are done in order to specify the substances that cause chemical sensitivities. We developed a chemical injection system that can control a room's chemical substance concentration uniformly (patent no.3027945).
*Challenge Test
This test is actually an examination done to determine the substances and quantities to which a patient with chemical sensitivities reacts.
System Flow